Login
Heat pump 2T IbriCal 6 kW

IbriCal 6 kW

Share

Heat pump 2T

  • Icona Plus

    COP 4,59

  • Icona Plus

    DHW 60°

  • Icona Plus

    WATER HEATING

  • Icona Plus

    WORKING RANGE -22°C / +45°C

  • Icona Plus

    HEATING

  • Icona Plus

    DHW

Technical specifications Technical Documentation Request info

IbriCal is the compact Hybrid System, made in Thermics. It is able to produce hot or cold water and to satisfy, depending on the season, the needs of heating, cooling of the building and production of DHW.
The system is composed of a condensing generator of the Thermodens or Thermodens Adaptive series in combination with a very high efficiency heat pump suitable for the most severe climatic conditions.

The advantages
• Quick and easy installation
• The F-gas patent is not required for installation
• Climate management included
• Compact 
• System intelligence is integrated into the PDC

Components

  1. Instantaneous condensing boiler 25 KW
  2. Control to the heat generator
  3. Wall mounted heat pump outlet - return
  4. Return of existing system *(only config. A)
  5. 20 litre tank
  6. Control to existing system
  7. Frame for wall mounting
  8. Heat pump

ibrical elementi

Where to install it?

  • Suitable for new energy efficient buildings
  • Suitable for building renovations
  • Suitable for harsh environments such as mountains and high T production up to 70°C
  • Suitable where there is no possibility to transport GAS
  • Suitable for applications with radiant systems, fancoils, air conditioning and UTA

ibrical schema

Winter operation

The winter operating modes are:

  1. Heat pump mode for heating: the unit produces hot water at the system side exchanger for heating; the production of DHW is guaranteed by the condensing heat generator.
  2. Hybrid mode, heat pump and boiler work synchronously managed by electronics specifically developed to guarantee maximum comfort. DHW management is always guaranteed by the boiler.
  3. Boiler mode, the heat generator intervenes to meet high temperature operating conditions or when external temperature conditions make the use of the heat pump uneconomic. DHW production is always guaranteed by the condensing boiler.

funz invernale

Summer operation

The summer operating modes are:

  1. Chiller mode: the unit only produces chilled water for the system.
  2. Boiler mode for the production of domestic hot water.

funz estivo

Automatic season regulation

The changeover from one mode to another takes place automatically referring to a logic of priority in the production of domestic water.

regolazione stagionale

Technical specifications

Winter operation A7/W35
Heat output 100%
kW
6,16
Heat output 66%
kW
4,21
Heat output 33%
kW
2,75
Compressor power input 100%
kW
1,18
Total power input 100%
kW
1,34
COP
4,59
System side
Water flow rate
m³/h
1,06
Useful head
mca
5,20
Pump power input
kW
0,06
Fan side
Air flow rate
m³/h
4000
Useful head
Pa
24,00
Power input
kW
0,10
Winter operation A7/W45
Heat output 100%
kW
5,99
Heat output 66%
kW
4,08
Heat output 33%
kW
2,66
Compressor power input 100%
kW
1,5
Total power input 100%
kW
1,65
COP
3,62
System side
Water flow rate
m³/h
1,03
Useful head
mca
6,5
Fan side
Air flow rate
m³/h
4000
Useful head
Pa
24,0
Power input
kW
0,10
Summer Operation A35/W18
Cooling capacity 100%
kW
8,05
Cooling capacity 66%
kW
5,58
Cooling capacity 33%
kW
3,70
Compressor power input 100%
kW
1,36
Total power input 100%
kW
1,52
EER
5,29
System side
Water flow rate
m³/h
1,39
Useful head
mca
5,60
Fan side
Air flow rate
m³/h
4000
Useful head
Pa
24
Power input
kW
0,10
Summer Operation A35/W7
Cooling capacity 100%
kW
5,62
Cooling capacity 66%
kW
3,87
Cooling capacity 33%
kW
2,55
Compressor power input 100%
kW
1,39
Total power input
kW
1,54
EER
3,64
System side
Water flow rate
m³/h
1,0
Useful head
mca
6,5
Fan side
Air flow rate
m³/h
4000
Useful head
Pa
24,0
Other data
Dimensions
mm
1000x735x443
Weight
kg
83
Refrigerant
R410a
Compressor
Twin Rotary
Number of compressors
1
Number of fans
1
Electrical supply
V/Ph/Hz
230-1-50
Water connections
1"
Sound pressure
dB(A)
59
Sound pressure at 1 m
dB(A)
57